Skip to main content

Thermolec

[gtranslate]
We are excited to announce that Thermolec is now a part of SPX Technologies, a supplier of highly engineered products and technologies, holding leadership positions in the HVAC and detection and measurement markets. Thermolec will integrate into the growing Electric Heat business platform of SPX’s HVAC segment alongside Marley Engineered Products and ASPEQ. Together, we’re expanding our capabilities and geographical presence to deliver even greater value to engineers, contractors, and building owners – offering more integrated solutions for today’s energy­-conscious world. This move presents a great cultural fit for Thermolec – and its employees and customers. We’re excited to join the SPX family! Read the full press release: Learn More

How is the SCCR rating determined?

The SCCR rating given for any heater is based on the lowest value of a component in the power circuit. If there are 4 components in the power circuit, the component with the lowest value is what determines the overall SCCR rating of the given heater.

What does “SCCR” stand for?

SCCR is short for “Short-circuit Current Rating”, the maximum current a device or system can safely withstand. This applies to all power components in a control panel. This is a request normally required by a device that must comply with UL508A. Although Thermolec does not comply with UL508A, we can still provide an SCCR rating […]

How does a voltage spike or drop affect the heater?

A spike or drop in the voltage of an electric heater will vary both the capacity (kW) and amp draw of the heater. Since an electric heater is a resistive load, and the element resistance is a fixed value, an increase in voltage will increase both the capacity and amp draw, and a drop in […]

What is FLA, MCA, and MOP/MOCP?

These are terms to describe amperage values for a heater. FLA stands for “Full-Load Amps”, the maximum nominal current of a heater. MCA stands for “Minimum Circuit Ampacity”, a calculated value with a safety factor that specifies the minimum main power supply and wires. MOP/MOCP stands for “Maximum Overcurrent Protection”, the highest current rating that […]

What is a PDS? Can the PDS be bypassed?

The PDS (Pressure Differential Switch) is a safety device used to enable/disable the heater’s operation when sufficient air flow is achieved. It closes when there is a minimum of 0.05” of static pressure. It is forbidden to bypass the PDS if it appears to be malfunctioning during operation. A chattering PDS means there are air […]

What is an electronic air flow sensor?

The electronic air flow sensor was designed specifically for VAV and CAV applications where the air flow may be too low, even below the recommended air flow. This is to be used in collaboration with modulating controls.

Can any thermostat be used with Thermolec heaters?

Thermolec can provide thermostats with any given heater upon request. If a different thermostat is to be used, make sure that the output capabilities of the thermostat is compatible with what was ordered. • Active 0-10VDC signal for modulating heaters (Similar to Thermolec’s CTH-291) • Passive Thermistor output for modulating heaters (Similar to Thermolec’s DT-1040 […]